Email: contact@reach-official.com
Air Insulated VCB 24kV
  • Details
  • Specification Parameters

The EcoAir-HBX-12/24kV 630A series represents a new generation of environmentally friendly, “fluorine-free and low solid waste” circuit breaker switches and gas-insulated ring main units designed as sustainable alternatives to traditional SF6 gas insulation.

This advanced circuit breaker switch features an integrated high-strength longitudinal beam that securely encases the vacuum arc extinguishing chamber, offering a robust structure and streamlined assembly. The unit performs opening, closing, and grounding functions through a precise, integrated isolation spindle mechanism, with no external transmission arms, ensuring accurate positioning and reduced operational force. Constructed with an epoxy fiberglass trigger rod, the main shaft offers high mechanical strength and excellent insulation. The mechanism, facilitated by an alloy bracket and cam, provides reliable vacuum arc extinguishing. Silicone umbrella skirts are applied between phases to extend the creepage distance and enhance safety. This circuit breaker switch is compatible with both sealed air chamber and normal-pressure metal-enclosed ring main units.

Employing an eco-friendly combination of gas insulation and vacuum interruption, this unit delivers high overall performance. The primary circuit is completely gas-sealed, unaffected by altitude, maintenance-free, and highly adaptable to environmental conditions. Its compact cabinet design optimizes space, making it ideal for deployment in power grids, large industries, rail transit, and commercial buildings.

Designed for indoor and outdoor use, this product serves as an efficient ring network switch in 10-24kV medium voltage distribution systems for energy distribution. Its modular design supports top and side expansion as well as common box configurations (up to three units). The upper and lower isolation parts share more than 90% common components, ensuring high stability, strong versatility, and full compliance with type testing standards.

 

Use Conditions

Normal environmental conditions:

 

EcoAir-HBX-24kV/630A generally operates/serves under normal indoor conditions and complies with IEC 62271-1 and GB3906.

 

The specific conditions are as follows:

 

1. Ambient temperature:

2. Maximum temperature: +40℃.

3. Maximum temperature (24-hour average): +35°C.

4. Minimum temperature: -40℃.

5. Maximum average relative humidity measured over 24 hours: 95%.

6. Maximum average relative humidity measured over one month: 90%.

7. The maximum altitude of installation without reducing gas pressure is 1500 meters. When the installation altitude exceeds 2500 meters, please contact pre-sales technology.

 

Special conditions:

 

Operation must comply with the requirements of IEC62271-1 and GB3906 standards. For special operating conditions, the end user and the manufacturer must reach an agreement. If special harsh operating environments are involved, the manufacturer must be consulted. For example, when electrical equipment is installed at an altitude above 1,500 meters, the atmospheric pressure will decrease, causing the air box to bulge.

Product Maintenance

All components inside the EcoAir-HBX-24kV 630A are maintenance-free for the declared product life.

The isolation and grounding positions can be observed to provide safety guarantee for operation and cable construction.

The system loop is completely isolated from the atmosphere, and a special arc pressure relief channel is designed on the air box to ensure the safety of operators and equipment.

 

The mechanical part is located outside the air box and behind the front panel, making it easier to operate and replace. The surface of the mechanical part has undergone anti-corrosion treatment, and its movable parts have been lubricated before leaving the factory, which can meet the use of the product life cycle. In extreme environments (dust, sand and dirt) inspection, maintenance and, in some cases, replacement may be necessary.


Special Customization

The Below parameters are typical data; if the existing styles do not meet your specific demands, please contact us for a custom design. We have significant personalized customization development and production skills, allowing us to provide tailored solutions to customers all over the world.

No.

Items

Unit

Vacuum Switch

Isolation / Grounding Switch

1

Rated voltage

kV

24

2

Rated current

A

630/1000

630/1000

3

Rated frequency

Hz

50/60

50/60

4

Rated short-circuit making current

kA

50

/

5

Rated short-circuit breaking current

kA

20/25

/

6

Rated short-time withstand current

kA

20

/

7

Rated peak withstand current

kA

50

/

8

Rated transfer current

A

/

/

9

Rated operating sequence


0-0.3s-CO-180s-CO


10

Rated power-frequency withstand voltage

kV

Between phases, to earth: 50/1min

Between phases, to earth: 50/1min




Across the isolating distance: 65/1min

Across the isolating distance: 65/1min




Auxiliary and control circuit: 2/1min

Auxiliary and control circuit: 2/1min

11

Rated lightning impulse withstand voltage

kV

Between phases, to earth: 125

Between phases, to earth: 125




Across the isolating distance: 145

Across the isolating distance: 145

12

Number of mechanical operations

bout

5000

3000

13

Resistance of main circuit

μΩ

≤200

≤200

14

Protection class: gas tank / cabinet


IP67/IP4X

IP67/IP4X

15

Partial discharge

Pc

18kV ≦ 20Pc


16

Standards


GB1984 GB3804 GB3906 IEC62271-100/105/200

IEC60265-1

 


Recommended for you

Contact Info

  • Xiamen Reach Tech Co., Ltd.  
  • Factory Building 2, No. 552 Tongji North Road, Tong'an District, Xiamen City, Fujian Province, China 361000
    Unit 201, No. 15, Tongfu Beili, Tong'an District, Xiamen City, Fujian Province, China 361000
  • Phone: +86 18150100999
  • Wechat: H_-1998
  • Whatsapp:
  • Mail: contact@reach-official.com